EFC 3610 - Frequency Converter
Giá bán: 0 VNĐ/cái
Số lượng
Giá thị trường: 0 VNĐ /cái Tiết kiệm: 0.0 %

Frequency converter

EFC 3610

 

 
   
  • Power range 1 x AC 230 V 0.4 kW to 3 x AC 400 V 22.0 kW
  • Integrated brake chopper and mains filter
  • Integrated operating panel for simple, fast commissioning
  • Expandability through I/O and fieldbus modules

 

 
Search
   
Search
 
Documentation  

Instructions   
PDF version  

PDF version   

Technical dataDimensionsCADDownloadOrder details

 
  EFC3610-0K40-1P2 EFC3610-0K75-1P2 EFC3610-1K50-1P2 EFC3610-2K20-1P2 EFC3610-0K40-3P4 EFC3610-0K75-3P4 EFC3610-1K50-3P4 EFC3610-2K20-3P4
Performance data
Rated output
HD operation
[kW] 0.4 0.75 1.5 2.2 0.4 0.75 1.5 2.2
Continuous rated current
HD operation
[A] 2.4 4.1 7.3 10.1 1.3 2.3 4 5.6
Motor rated voltage

Three phase, 0 V ... mains voltage

Output frequency

0 ... 400 Hz

Mains voltage 1 AC 1 AC 200 … 240 V (-10 % / +10 %) -
3 AC - 3 AC 380 … 480 V (-15 % / +10 %)
Frequency

50 ... 60 Hz (±5 %)

Overload capacity
HD operation

150 % for 60 s, 200 % for 1 s

Brake chopper / resistor
Braking resistance

External

Brake chopper

Internal up to 22 kW

Ambient conditions
Permissible temperature (operation)

-10 ... +45 °C (Derating 1.5 % of the output power per 1 °C from 45 ... 55 °C)

Permissible relative humidity (operation)

< 90 % (no condensation)

Max. installation height

1000 m (> 1000 m Derating 1 % of the output power pro 100 m)

Protection category

IP 20

Functions
Control technology

V/f

Pulse width modulation (PWM), adjustable in 1 kHz steps [kHz]

1 ... 15

Speed control range Without pulse generator

1 : 50

Start-up torque V/f

100% at 1.5 Hz; 150% at 3 Hz

Frequency resolution Digital

0.01 Hz

Analog

1/1000 of the output frequency

V/f curve

linear, quadratic, freely definable

Ramps

linear, S-curve

DC disc brake Start frequency

0 ... 50 Hz

Braking time

0 ... 10 s

Automatic PWM frequency adjustment

load-dependent adaptation of PWM frequency

Integrated control

integrated step switching mechanism

Frequency setting tolerance Analog

0.4 %

Digital

0.04 %

Controller

PID

Bus systems

Modbus RTU (with Multi-Ethernet Modbus TCP)

PROFIBUS, CANopen, Multi-Ethernet (ext. options)

Status messages via digital outputs

Operation, target value achieved, etc.

Number of digital inputs
24 VDC

5 (of which 1x pulse train 50 kHz)

Number of digital outputs
24 VDC / 50 mA

1 (pulse train 32 kHz)

Number of relay outputs 
230 VAC / 30 VDC / 3 A

1

Number of analog inputs
0 ... 10 V or 0 ... 20 mA

2

Number of analog outputs
0 ... 10 V or 0 ... 20 mA

1

Display

Dust cover with 4 diagnostic LED

LED 5 digit (optional)

LCD (optional)

Status LED

Rotation direction and operating status

Weight
Weight [kg] 1.5 1.9 2.6 1.5 1.9
Norms and Standards
Certification

CE
UL
cUL
EAC
C-Tick (RCM)

 
  EFC3610-3K00-3P4 EFC3610-4K00-3P4 EFC3610-5K50-3P4 EFC3610-7K50-3P4 EFC3610-11K0-3P4 EFC3610-15K0-3P4 EFC3610-18K5-3P4 EFC3610-22K0-3P4
Performance data
Rated output
HD operation
[kW] 3 4 5.5 7.5 11 15 18.5 22
Rated output
ND operation
[kW] - 7.5 11 15 18.5 22 30
Continuous rated current
HD operation
[A] 7.4 9.7 12.7 16.8 24.3 32.4 39.2 45
Continuous rated current
ND operation
[A] - 16.8 24.3 32.4 39.2 45 60.8
Motor rated voltage

Three phase, 0 V ... mains voltage

Output frequency

0 ... 400 Hz

Mains voltage 3 AC

3 AC 380 … 480 V (-15 % / +10 %)

Frequency

50 ... 60 Hz (±5 %)

Overload capacity
HD operation

150 % for 60 s, 200 % for 1 s

Brake chopper / resistor
Braking resistance

External

Brake chopper

Internal up to 22 kW

Ambient conditions
Permissible temperature (operation)

-10 ... +45 °C (Derating 1.5 % of the output power per 1 °C from 45 ... 55 °C)

Permissible relative humidity (operation)

< 90 % (no condensation)

Max. installation height

1000 m (> 1000 m Derating 1 % of the output power pro 100 m)

Protection category

IP 20

Functions
Control technology

V/f

Pulse width modulation (PWM), adjustable in 1 kHz steps [kHz]

1 ... 15

Speed control range Without pulse generator

1 : 50

Start-up torque V/f

100% at 1.5 Hz; 150% at 3 Hz

Frequency resolution Digital

0.01 Hz

Analog

1/1000 of the output frequency

V/f curve

linear, quadratic, freely definable

Ramps

linear, S-curve

DC disc brake Start frequency

0 ... 50 Hz

Braking time

0 ... 10 s

Automatic PWM frequency adjustment

load-dependent adaptation of PWM frequency

Integrated control

integrated step switching mechanism

Frequency setting tolerance Analog

0.4 %

Digital

0.04 %

Controller

PID

Bus systems

Modbus RTU (with Multi-Ethernet Modbus TCP)

PROFIBUS, CANopen, Multi-Ethernet (ext. options)

Status messages via digital outputs

Operation, target value achieved, etc.

Number of digital inputs
24 VDC

5 (of which 1x pulse train 50 kHz)

Number of digital outputs
24 VDC / 50 mA

1 (pulse train 32 kHz)

Number of relay outputs 
230 VAC / 30 VDC / 3 A

1

Number of analog inputs
0 ... 10 V or 0 ... 20 mA

2

Number of analog outputs
0 ... 10 V or 0 ... 20 mA

1

Display

Dust cover with 4 diagnostic LED

LED 5 digit (optional)

LCD (optional)

Status LED

Rotation direction and operating status

Weight
Weight [kg] 2.6 3.9 4.3 5.7 6.4 8 8.5
Norms and Standards
Certification

CE
UL
cUL
EAC
C-Tick (RCM)

 

Electric Drives and Controls, Online Version, Last Updated #version#

© Bosch Rexroth AG, Subject to Change

(*) là thông tin bắt buộc
(*)
(*)
(*)
synthroiduuu
06/05/2023 18:37:58
over the counter thyroid pills Synthroid is usually taken once a day, on an empty stomach, and it is important to take it at the same time each day. The dose of Synthroid is based on the patient's weight, age, and the severity of their hypothyroidism. It is important to follow the dosing instructions provided by the doctor, as taking too much or too little Synthroid can lead to side effects or reduced effectiveness.
synthroidvbo
06/05/2023 16:05:02
where can i buy levothyroxine Patients with hypothyroidism may require regular blood tests to monitor thyroid hormone levels and ensure that the medication is working effectively. Patients should also inform their doctor if they have any medical conditions such as heart disease, diabetes, or adrenal gland problems, as these conditions can affect how levothyroxine is dosed and may require additional monitoring.
synthroidtro.com
06/05/2023 15:01:52
levothyroxine 150 mcg cost Patients should not stop taking Synthroid or levothyroxine without consulting their healthcare provider, as abruptly stopping the medication can cause withdrawal symptoms or worsen thyroid function.
synthroidtro
06/05/2023 14:09:04
levothyroxine 100 mcg picture Like other medications, levothyroxine can interact with other drugs and supplements, and patients should inform their doctor of all medications and supplements being taken.
synthroidtro
06/05/2023 13:26:03
synthroid 200 mcg price Patients should inform their healthcare provider if they have a history of heart disease, as Synthroid or levothyroxine can affect heart function.
Frequency Converter
0 VNĐ
Frequency Converter
0 VNĐ
Frequency Converter
0 VNĐ